Where would we bond the grounded and grounding conductors?
The neutral and equipment grounding conductor are required by the National Electrical Code (NEC) to be bonded at the main service panel and the secondary side of a separately derived system (more on this below). Only one neutral to ground bond is permitted by the NEC to exist on each separately derived system.
Can be used to connect grounding conductors and bonding jumpers?
Grounding conductors and bonding jumpers shall be connected by exothermic welding, listed pressure connectors, listed clamps, or other listed means. Not more than one connector can be connected to the grounding electrode by a single clamp or fitting unless the clamp or fitting is listed for multiple conductors.
What connects the equipment grounding conductors to the grounded conductors?
A grounding electrode conductor (GEC) connects the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system (see Article 100 definition of Grounding Electrode Conductor).
Is a conductor used to connect the system grounded conductor?
Grounding electrode conductor: A conductor used to connect the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system.
What is the purpose of grounding and bonding?
Bonding and grounding work together to ensure all components are on a ground-fault path. This protects systems and personnel and helps circuit breakers and ground-fault detectors work properly. Systems that are bonded but not grounded are called floating systems, and do not offer the same level of protection.
Is the connection between the grounded circuit conductor and the equipment grounding conductor or the supply side bonding jumper or both at the service?
System bonding jumper — The 2011 NEC defines the system bonding jumper as “the connection between the grounded circuit conductor and the supply-side bonding jumper, or the equipment grounding conductor, or both, at a separately derived system.” The objective of the system bonding jumper is to connect the grounded …
How is the grounding conductor connected?
1 Methods of Grounding Conductor Connection to Electrodes. The grounding or bonding conductor shall be connected to the grounding electrode by exothermic welding, listed lugs, listed pressure connectors, listed clamps or other listed means. Connections depending on solder shall not be used.
What is the difference between the grounded conductor and the grounding conductor?
Grounded vs. Sometimes the neutral wire is referred to as a grounded wire. It is most correctly referred to as a “grounded neutral conductor,” but most times referred to as “the neutral” or “the ground wire”. A “grounding” wire on the other hand is a safety wire that has intentionally been connected to earth.
What are bonding conductors?
Supplementary bonding conductors. These conductors connect together extraneous conductive parts – that is, metalwork which is not associated with the electrical installation but which may provide a conducting path giving rise to shock.
What is the difference between grounded and grounding conductor?
Sometimes the neutral wire is referred to as a grounded wire. It is most correctly referred to as a “grounded neutral conductor,” but most times referred to as “the neutral” or “the ground wire”. A “grounding” wire on the other hand is a safety wire that has intentionally been connected to earth.
What is the difference between grounding and bonding?
Bonding is the connection of non-current-carrying conductive elements like enclosures and structures. Grounding is the attachment of bonded systems to the earth. Both are necessary to safeguard people and property from electric hazards.
What is the connection between a grounding and bonding jumper?
Bonding Jumper, System— The connection between the grounded circuit conductor and the supply-side bonding jumper, or the equipment grounding conductor, or both, at a separately derived system. Sizing Grounding Electrode Conductors
How is a grounding conductor used in an electrical system?
Grounding Electrode Conductor— A conductor used to connect the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system. This is the conductor that connects the grounding electrodes to the electrical system. Ground-Fault Current Path— An electrically conductive path
Which is the best standard for grounding and bonding?
For a designer of telecommunications bonding and grounding systems, the ANSI/TIA-607-B standard is the most encompassing standard to follow for premises buildings.
How are grounded media bonded to lightning grounding system?
Grounded media and buried metallic conductors shall be bonded to the lightning protection grounding system below a height 12 ft. (3.6 m) vertically above the base of the structure. Grounded media and buried metallic conductors inherently bonded through construction to the lightning protection grounding system shall not require further bonding.